Cooling Capacity | ×1000 kcal/h | 7.9 | 12.8 | 20.8 | 27.9 | 32.3 | 40.8 | 55.7 | 64.7 | 81.5 | 97.0 | 122.3 | |
KW | 9.2 | 14.9 | 24.2 | 32.4 | 37.6 | 47.4 | 64.8 | 75.2 | 94.8 | 112.8 | 142.2 | ||
Input Power (KW) | 3.85 | 5.55 | 8.15 | 10.4 | 12.0 | 16.0 | 20.1 | 22.5 | 31.2 | 33.7 | 45.7 | ||
Comp. Input Power×Qty.  (KW) | 2.6 | 4.3 | 6.35 | 8.1 | 9.3 | 12.5 | 8.1×2 | 9.3×2 | 12.5×2 | 9.3×3 | 12.5×3 | ||
 Chilled Water Pump Power  (KW) | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.5 | 1.5 | 1.5 | 2.2 | 2.2 | 2.2 | ||
 Comp. Current (A) | 6.8 | 10.5 | 14 | 17.5 | 20 | 25.6 | 33.8 | 37.2 | 49.8 | 55.8 | 72.6 | ||
Power Supply | 3φ-380V-50HZ | ||||||||||||
 Safety Protection | Phase reversion protection, Phase lack protection, Overload current protection, Discharge air temp.  protection, Low & High pressure protection, Low temp.  protection, Water flow protection, |
||||||||||||
 Number of Refrigeration Circuit | 1 | 2 | 3 | ||||||||||
 Capacity Control (%) | 0, 100 | 0, 50, 100 | 0, 33, 66, 100 | ||||||||||
 Refrigerant | R22 | ||||||||||||
 Condenser | Ripple Aluminum Fins around Cooper Pipe | ||||||||||||
 Power lnput of Fan (KW) | 0.5 | 0.5 | 0.7 | 1.2 | 1.2 | 2.0 | 2.4 | 2.4 | 4.0 | 3.6 | 6.0 | ||
 Evaporator | Pipe Coil Type | ||||||||||||
 Water Side Max Pressure (MPa) | - | 1 | |||||||||||
 Dia.of Pipe to Evaporator (inch) | 1" | 1-1/2" | 2" | 2-1/2" | |||||||||
 Chilled Water Flow (L/m) | 26.4 | 42.7 | 69.4 | 92.9 | 107.8 | 135.9 | 172.0 | 194.8 | 272.2 | 292.2 | 408.3 | ||
 Evaporator Water Pressure drop (kPa) | - | 17 | 23 | 28 | 30 | 28 | 28 | 32 | 32 | 31 | |||
 Running Noise dB(A) | 72 | 72 | 73 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | ||
 Tank Volume (L) | 50 | 70 | 120 | 200 | 200 | 270 | 350 | 350 | 420 | 510 | 510 | ||
 Total weight (Kg) | 130 | 170 | 430 | 480 | 510 | 560 | 840 | 880 | 980 | 1130 | 1280 |
A: Generally, for industrial water chiller we need to know the following information in order to suggest the suitable water chiller
models and for providing the quotation.
1) Air cooled or water cooled?
2) Cooling Capacity.
3) Power Supply.
4) Refrigerant.
5) Chilled water outlet temperature.
6) Evaporator need pipe coil type or shell and tube type.
7) With water pump and water tank or not.
8) Order Quantity etc.
Our standard industrial scroll water chiller is 380V/3P/50Hz, refrigerant R22, chilled water outlet is 5~20Deg.
With water pump and S/SÂ water tank, the evaporator is pipe coil type in the water tank.
Q:Â Can I have a samples for testing before ordering products?
A:Â Yes, you can.
We sincerely suggest that customers should have some samples of required fans for testing because the truly performance
of fans can be fully demonstrated after testing is conducted.
Q:Â What is the warranty of products?
A: For 1 year warranty. Free to amend and change the parts due to quality reasons in warranty year.